Copyright © Huawei Technologies Co., Ltd.
is too high.
The battery string
overdischarges.
batteries in a timely manner.
Check whether the BCB box
runs properly.
Check whether the
connection between the
BCB box and the board is
normal.
Battery
management
module fault
The relay of the battery
management module is
arcing.
The auxiliary power
supply of the battery
management module is
abnormal.
The balanced circuit works
abnormally.
The hardware
overtemperature protection
signal is valid.
The battery management
module is abnormal.
The intra-rack parallel
cable is faulty.
The voltage sampling
circuit is faulty.
The current CT sampling
circuit is faulty.
The battery input cable is
not connected.
The battery input fuse is
open-circuited.
Check the battery cable
connection.
Check whether the ambient
temperature is too high.
Replace the input fuse.
Replace the battery
management module.
Battery
overcurrent
protection
The load exceeds the upper
threshold.
The battery charge or
discharge current reaches
the protection threshold.
The charger of the battery
management module is
faulty.
The battery management
module is damaged.
Check whether the load of
UPS exceeds the battery
configuration.
Replace the battery
management module.
The emergency shutdown
signal of the battery cabinet is
Manually clear the EPO state.