Copyright © Huawei Technologies Co., Ltd.
Lithium battery
system
communication
failure
The communication between
the UPS monitoring unit and
the lithium battery is
interrupted.
Check the cable between the
UPS monitoring unit and the
lithium battery.
Lithium battery
capacity
mismatch
The number of configured
UPS modules exceeds the
upper limit supported by the
lithium battery cabinet.
Reduce the number of UPS
modules or add a lithium
battery cabinet.
Battery module
not detected
The battery management
module does not receive an
online query response from
the battery module.
Check whether the signal
terminal of the battery
module is properly
connected.
Replace the battery module.
Battery module
balance alarm
There is no enough time
for cell balancing.
The cell balancing cable is
faulty.
The electrochemical cell
temperature consistency is
poor.
Charge batteries for at least
3 days, and then check
whether the alarm
disappears.
Replace the battery module.