SmartLi
User Manual
5 Operations
Copyright © Huawei Technologies Co., Ltd.
75
The UPS is working in normal mode; float charging or hibernation has lasted for 2 hours
after the state of charge (SOC) reaches 100%; and the load ratio fluctuation is less than
10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
The SmartLi has generated no alarms related to lithium batteries.
Automatic Shallow Discharge Test
1. On the home screen of the UPS LCD, choose System Info > Settings > Battery
Settings and set Sched. shallow dis. test to Enable.
2. Set Sched. shallow dis. test time and Sched. shallow dis. test interval as required.
After setting is complete, the system will perform automatic shallow discharge tests
based on the settings.
Manual Shallow Discharge Test
1. On the home screen of the UPS LCD, choose System Info > Maintenance > Battery
Maint.
2. Tap Start next to Shallow Dis. Test to start a shallow discharge test.
Figure 5-7 Starting a shallow discharge test
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).
The load ratio fluctuation exceeds 10%.
An alarm is generated.