the region within 500 m from the coast or prone to sea breeze. The eect
from sea breeze depends on weather conditions (such as typhoon and season
wind) or terrains (such as dams and hills).
Site Requirements
The SUN2000 should be installed in a well-ventilated environment to ensure
good heat dissipation.
If the SUN2000 is installed in a place exposed to direct sunlight, the power
may decrease as the temperature rises.
You are advised to install the SUN2000 in a sheltered place or install an
awning over it.
Mounting Structure Requirements
The mounting structure where the SUN2000 is installed must be
re resistant.
Do not install the SUN2000 on
ammable building materials.
The SUN2000 is heavy. Ensure that the installation surface is solid enough to
bear the weight load.
In residential areas, do not install the SUN2000 on drywalls or walls made of
similar materials which have a weak sound insulation performance because
the noise generated by the SUN2000 is noticeable.
Installation Angle Requirements
The SUN2000 can be wall-mounted or support-mounted. Requirements for the
installation angle:
Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to
facilitate heat dissipation.
Do not install the SUN2000 with a front tilt, excessive back tilt, side tilt,
horizontally, or upside down.
Figure 4-1 Installation angle
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 4 Installation
Issue 11 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 24

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-M3 and is the answer not in the manual?

Huawei SUN2000-M3 Specifications

General IconGeneral
TypeString Inverter
Rated AC Grid Frequency50 Hz / 60 Hz
DC Connection TypeMC4
Protection DegreeIP65
Cooling MethodNatural convection
CategoryInverter
Adjustable Power Factor Range0.8 leading - 0.8 lagging
Total Harmonic Distortion (THD)≤ 3 %
Operating Temperature Range-25°C to 60°C
CommunicationRS485
Efficiency98%
Protection LevelDC reverse polarity protection, AC overcurrent protection, AC short-circuit protection, Overvoltage protection, Insulation monitoring, Residual current monitoring unit, Arc fault detection

Related product manuals