Technical
Specications
SUN2000-20K
TL-M3
SUN2000-29.
9KTL-M3
SUN2000-30K
TL-M3
SUN2000-36K
TL-M3
SUN2000-40K
TL-M3
Maximum
total
harmonic
distortion
(THD)
AC THDi
< 3% under rated conditions. Single harmonic meets the VDE4105 requirements.
Note a: Under the Germany VDE-AR-N-4105, Belgium C10/11, and Austria TOR grid codes, the
maximum apparent power and the maximum active power (cosΦ=1) of the SUN2000-30KTL-M3
are 30,000 VA and 30,000 W respectively.
Protection
Technical
Specications
SUN2000-20K
TL-M3
SUN2000-29.
9KTL-M3
SUN2000-30K
TL-M3
SUN2000-36K
TL-M3
SUN2000-40K
TL-M3
Overvoltage
category
PV II/AC III
Input DC
switch
Supported
Islanding
protection
Supported
Output
overcurrent
protection
Supported
Input reverse
connection
protection
Supported
String fault
detection
Supported
DC surge
protection
Type II
AC surge
protection
Type II
Insulation
resistance
detection
Supported
Residual
current
monitoring
unit (RCMU)
Supported
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 10 Technical Specications
Issue 11 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 90

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-M3 and is the answer not in the manual?

Huawei SUN2000-M3 Specifications

General IconGeneral
TypeString Inverter
Rated AC Grid Frequency50 Hz / 60 Hz
DC Connection TypeMC4
Protection DegreeIP65
Cooling MethodNatural convection
CategoryInverter
Adjustable Power Factor Range0.8 leading - 0.8 lagging
Total Harmonic Distortion (THD)≤ 3 %
Operating Temperature Range-25°C to 60°C
CommunicationRS485
Efficiency98%
Protection LevelDC reverse polarity protection, AC overcurrent protection, AC short-circuit protection, Overvoltage protection, Insulation monitoring, Residual current monitoring unit, Arc fault detection