Flow-Clik will not shut the
irrigation system off
No power to Flow-Clik
Faulty wire connections from the
Flow-Clik sensor to the Interface Box
System has not reached an overow
condition
System is in the Startup Delay mode
Check System Status Indicator light is on (if light is off, see
above).
Check Flow-Clik sensor wires (red and black wires) are properly
connected.
A) Normal operation.
B) System is not balanced. Too much variation between ow rates
of the zones may prevent the Flow-Clik from sensing an overow
condition on the lower ow zone(s). Flow-Clik can only sense
ows above the system maximum.
Wait for start up delay period to end.
Flow-Clik continually shuts
off a zone with no known
problems
Flow-Clik is improperly calibrated
High uctuations in system pressure
Reset the Flow-Clik to the highest ow zone.
It is recommended that the Flow-Clik be set at the time of day
that the irrigation system will be run. Note: If too much pressure
uctuation occurs, it may be necessary to add pressure regulation
to the system.