SPA
Page 49
.
Changing the system date corresponds to the operating sequence for
the system time.
Setting the Timer Mode
There are three possible settings for the time clock:
off: time clock is disabled
weekly: every day the steam generator is released for the same
period of time
•daily: for each weekday the steam generator is released for a
special period of time
The setting:
Within the submenu „Time Clock“ press until „Timer Mode“
appears. Select the „Timer Mode“ submenu by pressing and
choose between the three possible settings with . By pressing
the choosen setting is stored. If a daily or weekly timer mode is
choosen press for putting in the respective switch-on and
switch-off times [hh:mm] (T1 and T2 = weekly operating period; T3 and
T16 daily operating period).
U5 Pumping without K1 (main contactor deactivated during blow-
down)
With this parameter, one can specify the switching status of the “On” /
“Off” contactor during blow-down. At the “on” setting, the control will
switch off the contactor during the blow-down procedure. This setting
could be useful if the power supply line is routed through a sensitive
residual-current-operated circuit breaker (rccb).
U6 Operating Mode
With parameter U6, one can set the humidifier control type.