Fault Main Con-
tactor
Unit shuts off auto-
matically
Main contactor does not drop out.
Relay on the PCB is stuck.
Replace main contactor.
Replace PCB.
XX
Fault °C sensor Temperature sensor or line defective. Check temperature sensor and
sensor line, replace if needed.
Unit shuts off auto-
matically.
Short circuit in sensor wire (no resistance). Replace temperature sensor.
Fault sensor
X Unit shuts off auto-
matically.
Cable connections for the float switch are
faulty.
Plug for the float switch is not connected to he
control
Check cable connections, replace if
needed.
Connect plug to the control.
XX
Fault °C Max
Unit shuts off auto-
matically.
Heat buildup in the cabin. Ensure continuous heat removal.
Additional heat source in the steam cabin.
Excessive power retention check Parameter G9
X
Fault Activated
Thermo Sensor
Unit shuts off auto-
matically.
Thermo sensor on the top of the cylinder has
been activated (HeaterLine = 2 thermo sen-
sors, HeaterCompact = 1 thermo sensor).
Heating element is coated by lime.
Thermosensor on the heat sink for the solid
state relay has been activated. Openings for
chimney are covered.
Disconnect power supply. Wait un-
til cylinder has cooled down. Press
the release pin back down with
needle-nose pliers a or a screw-
driver.
Remove lime.
Press the release pin back down
and remove the blocking elements.
LED Dis-
play
HL ***
Hy,C***
Message / Mal-
function Dis-
played*
Probable Cause Resolution