Page 21
A: Humidification
B: Dehumidification
C: .Rel. Humidity % RH
Example:
P8 Set value RH = 50%
E18 Offset for Dehumidifier =
5%
Switchover point humidifica-
tion - Dehumidification =
55% + 1% hysteresis
In this example, the dehumidi-
fier switches on at 56% RH and
switches off at 55% RH.
Note: To use this function, the
base relay or one of the
optional signal relays must be
programmed for the function
“dehumidification” and the
dehumidifier must be con-
nected to this relay.
Basic
Comfort / Comfort Plus