9. Malfunctions and Messages / Conditions
Switch off the steam humidifier immediately if a fault occurs!
Faults are only to be remedied by qualified personnel following the pro-
per safety instructions.
The fault messages displayed depend on the humidifier type in
use; in the table below, “HE” denotes heater element steam
humidifiers and “ESH” denotes steam humidifiers. Some fault
messages are identical with both humidifier types.
Please note
LED
Display
HE ***
ESH***
Message / Mal-
function Dis-
played*
Probable Cause Resolution
X
X
Blow-Down
Fault
Unit shuts off au-
tomatically
Blow-down pump has not been electrical-
ly activated
- Cable connections are faulty
- The relay on the main PCB is not oper-
ating
Check or replace cable connec-
tions
Measure voltage at the PCB ter-
minals against N or replace
PCB
Defective blow-down pump Replace blow-down pump.
Solenoid valve does not close properly.
Water level in the cylinder sinks very
slowly even though blow-down pump
flushes out water.
Check solenoid valve.
Blow-down pump operates, but no water
is pumped out, i.e. the cylinder drain is
blocked.
Thouroughly clean steam cylin-
der and base to prevent short-
term blockage from reoccurring
Blow-down pump is blocked up with min-
eral deposits.
Check blow-down pump, drain
assembly and cylinder for min-
eral deposits and clean.
X
Max.-Level Fault
Unit shuts off au-
tomatically.
If the water level “max. level” is reached,
the pump switches on and drains the cyl-
inder until the water level lowers to “oper-
ation.” If the “max.-level” is reached five
times, “max.-level” is displayed.
Air pressure in the duct is too high. Duct
air pressure enters the cylinder via the
steam hose. Water is forced into the
drain.
Reduce air pressure or detach
vent pipes from the unit and
place higher