No partial and total cylinder blow-downs are necessary when
using fully demineralized water. The “fully demineralized water”
function prevents blow-downs.
This function should not be activated when using electrode
steam humidifiers of Type HyLine, CompactLine or MiniSteam.
Jumper I
The standard setting for this jumper is open.
Note: This jumper may not be jumpered or only jumpered after
consultation with HygroMatik.
Jumper J
The standard setting for this jumper is open. This jumper may
not be jumpered or only jumpered after consultation with Hygro-
Matik.
Jumper K
The standard setting for this jumper is open.
This jumper may not be jumpered or only jumpered after consul-
tation with HygroMatik.
Jumper L
The standard setting for this jumper is open.
This jumper may not be jumpered or only jumpered after consul-
tation with HygroMatik.
Jumper E and J inverted
After the preprogrammed number of operations of the main con-
tactor (K1) the HygroMatik control provides the message "Main-
tenance K1". During this, the green LED blinks rapidly. By
appropriately setting of the jumpers, this message can be reset.
Therefore please turn off the unit and identify the status (open or
closed) of the jumpers E and J. By inserting or removing the
jumpers create inverted status of jumpers. Turn on the unit for
about 5 seconds. Then turn off the device and restore the old
status of the jumpers. This resets the message.