Water is leaking
from upper part of
steam cylinder.
Hose clamps on the steam or condensate
hose do not close tightly.
Tighten hose clamps.
XX The heater element or thermo sensor has
not been properly installed.
Install heater element and ther-
mo sensor as specified in the
unit manual.
Steam hose adapter has not been cor-
rectly installed or o-ring has not been
changed.
Replace o-ring and correctly in-
stall steam hose adapter.
If condensate is not into the steam cylin-
der, the condensate connection must
have a condensate plug.
Install condensate plug.
XX
No steam produc-
tion even though
the steam gener-
ator is on.
The display is
dark
Defective fuse F1 1.6 A.
Phase failure L3. (External breaker has
been tripped or is defective.)
Check micro fuse and replace,
also see Section „Wiring dia-
gram“.
Replace external breaker and
investigate possible causes.
XX
Blow-down pump
is working, but no
water is being
flushed
Cylinder base or blow-down system is
blocked.
Clean cylinder base or blow-
down system.
XX
Cylinder has
completely
drained after a
blow-down, even
though pump is
switched off.
Vent pipe is blocked. Clean or replace vent tube. Re-
place vent pipe adapter.
Also see unit manual.