Table 36. Warning events (continued)
Event Code Message Text and Description Details and Solution
4080 Library Verify test failed with warning. An unidentied failure occurred. Contact your
IBM service representative.
4085 Drive command retries expired.
• Run a drive read/write test (Library > Actions
> Tests > Drive test) with a known working
cartridge.
• If the drive test is successful, check in the
host for errors that are related with the
retries.
• If the drive test failed, replace the drive.
4086 Move operation failed.
• Ensure that the network the library is
connected to is operating normally.
• Ensure that the library is running the current
rmware.
• Restart the library.
4089 Auto calibration of one or more modules
failed. Adjustment to calibration target
failed.
• The library must be recalibrated.
• Ensure that the library rmware is up-to-
date.
• This event indicates that one or more of the
gray calibration targets on the library
magazines couldn’t be used in calibration.
• Inspect the calibration targets in each
module and then repeat the auto-calibration
routine with the Management GUI.
4090 Auto calibration of one or more modules
failed. Calibration target not found
• The library must be recalibrated.
• Ensure that the library rmware is up-to-
date.
• This event indicates that one or more of the
gray calibration targets on the library
magazines couldn’t be used in calibration.
• Inspect the calibration targets in each
module and then repeat the auto-calibration
routine with the Management GUI.
4091 Auto calibration of one or more modules
failed. Adjustment out of range
• The library must be recalibrated.
• Ensure that the library rmware is up-to-
date.
• This event indicates that one or more of the
gray calibration targets on the library
magazines couldn’t be used in calibration.
• Inspect the calibration targets in each
module and then repeat the auto-calibration
routine with the Management GUI.