section of the Network Setup tab and on the Help tab. The unique unit MIB
file must then be imported into the external SNMP management software.
Enable SNMP: Select this check box to enable the SNMP agent. The
default setting is Disabled.
SNMP Version: Set the SNMP version (v1/v2c, v3, or All) supported by
the SNMP agent. If "All" is selected, all SNMP versions will be supported
simultaneously. The appropriate settings for the selected SNMP version
will need to be configured.
Enable SNMP Write Access: Select this check box to enable DC power
to individual outputs through SNMP. If this box is unchecked, all
information available from the SNMP agent will be read-only.
SNMP Control Access: Set the level of unit control that is allowed
through SNMP. This setting is only available if Enable SNMP Write
Access is enabled.
• Output Control: Allows remote SNMP control of the system
output and LDM channel outputs only.
• Full Device Control: Allows SNMP client to set all unit settings
through SNMP. This setting requires a different MIB file which can
be downloaded from the ICT Website: https://www.ict-
power.com/resources/tools-utilities/.
SNMP Contact Information: Set contact information, such as an
operator name and phone number for the unit, which can be read via
SNMP queries (this information is optional).
v1/v2c Settings
Read Community: Enter the community string/password here for read-
only SNMP access. The default read community string is "public".
Write Community: Enter the community string/password here for
read/write SNMP access. The default write community string is "write".
NOTE: The community strings should be changed to unique passwords
before enabling SNMP, as the defaults are well known.
v3 Settings
User Name: Set the username for SNMPv3 access.
Authentication Protocol: Set the SNMPv3 authentication protocol
(None, MD5, or SHA).