NOTE: Due to the breaker-detection circuitry internal to the unit, it may be
possible to measure a voltage on the terminal(s) with no load
connected, even if that terminal’s breaker is open circuit. This is
normal operation. The breaker-detection circuitry is a high-
impedance circuit, and while a voltage may be present on the output
terminal, it is a signal voltage and does not support loading. A load
device connected to the output will immediately pull this voltage to
zero volts.
Product Alerts
Risk of personal injury or damage to equipment and
property. Always observe the following:
• Ensure the total power consumption of the loads does not
exceed the 100 amps (peak) rated capacity of each power
bus.
• Ensure continuous load current through each output
channel does not exceed the 80% of the maximum output
ratings in accordance with NEC Section 210.20(A).