EasyManua.ls Logo

INFOSEC E6 LCD-RT Evolution - Battery; Display; Audible Alarms; Management; Communication

INFOSEC E6 LCD-RT Evolution
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr 05 13 AA 59 208 13
25
E6 LCD RT
EVOLUTION
5000 (S)
E6 LCD RT
EVOLUTION
6000 (S)
E6 LCD RT
EVOLUTION
8000 (S)
E6 LCD RT
EVOLUTION
10000 (S)
BATTERY
12 V / 7 AH 12 V / 7 AH 12 V / 9 AH 12 V / 9 AH
Recharging voltage
20** 20** 20** 20**
7 hours recover to
90% capacity
7 hours recover to
90% capacity
9 hours recover to
90% capacity
9 hours recover to
90% capacity
AUDIBLE ALARMS
ENVIRONMENT
- - - -
600 W / 2047,8
Btu/h
600 W / 2047,8
Btu/h
600 W / 2047,8
Btu/h
600 W / 2047,8
Btu/h
NORMS
SALES INFO
3700085 67119 1 3700085 67120 7 3700085 67121 4 3700085 67122 1
3700085 67123 8 3700085 67124 5 3700085 67125 2 3700085 67126 9
Communication
2 years
CE RoHS, cTUVus
Gencods - standard versions
Gencods - Long backup time version (S)
Heat dissipation max - HV (230 V)
Heat dissipation max - LV (110 V)
MANAGEMENT / COMMUNICATION
Number
Typical recharge time
Charging current (max)
1A
Backup time
From 4 to 30 minutes depending on the connected load
240 Vdc
240 Vdc
Long backup time model (S)
Typical recharge time
Depending on the capacity of external batteries
Charging current (max)
4A
Low battery
Sounding every second
Overload
Battery mode
Sounding every 4 seconds
LCD screen
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
DISPLAY
Optional SNMP
Standard
EN 62040-2 : 2006
EN62040-1 : 2008, UL1778/R:2006;CSA C22.2 NO.107.3-05/R:2006
Parallel port
Parallel connection
Up to 1000 m above sea level (> 1000 m 1% deterioration for every 100 m)
Sounding twice every second
Warranty
USB & RS232 port and Infopower included software
(support Windows family, Linux, Unix and MAC)
Standard model
Battery type
Operating Altitude
Ideal environment
0 - 95% relative humidity @ 0-40° non condensing
Noise level
less than 58dBA @ 1 meter
less than 60dBA @ 1 meter
EMC (Electromagnetic compatibility)
Low voltage (Safety)
Fault
Continuously sounding
* LV (110V) and HV (230V) are different products
** When using internal batteries from 18-19, the unit will de-rate according to below formula : P=Prating x N/20
Product specifications are subject to change without further notice.