Commissioning Procedure IS300 Series Servo Drive User Manual
- 32 -
4. A3-00=3: Oil pressure control mode (special use)
The servo pump control parameters in group A3 are invalid.
5. A3-00=4: Reserved.
3.3.3 Automatic Setting of Parameters in Oil Pressure Control
When the non-oil pressure mode switches to the oil pressure mode (A3-00≠"0"), the related
parameters will be set automatically set. See the following table for details.
Function Code Name Setting
F0-01 Control mode 1: Vector control (VC)
F0-02 Command source selection 1: Terminal input (LED indicator on)
F0-03 Main frequency source X
selection
If A3-00=2, set F0-03 to 3 (AI2). If A3-00=1
or 3, set F0-03=9 (via communication).
F0-07 Frequency source selection 0: Main frequency source X
F0-17 Acceleration time 1 0.0s
F0-18 Deceleration time 1 0.0s
F1-00 Motor type selection 2: PMSM
F4-00 DI1 function selection 1: Forward RUN (FWD, pump enabled)
F4-01 DI2 function selection 48: Servo pump PID selection terminal 1
F4-02 DI3 function selection 49: Servo pump PID selection terminal 2
F4-03 DI4 function selection 9: Fault reset (RESET)
F4-04 DI5 function selection 50: CAN COM enabled
F5-01 Control board relay (T/A1-T/
B1-T/C1) output selection
2: Fault output
F5-02 Control board relay
(T/A2-T/C2) output selection
23: Double-discharge plunger pump
sloping switchover (NO)
F5-03 Control board relay
(T/A3-T/C3) output selection
24: Output NC in pressure control
These parameters are retentive at power failure in the oil pressure control mode. They
will restore to the automatically set value once the servo drive is re-powered on. Once the
system is switched over from oil pressure control to non-oil pressure control, the parameters
will restore to the value that was set before system switch-over to the oil pressure control.
3.3.4 Setting of ow and Oil Pressure Commands
• A3-01: Max. rotational sped
Set the maximum motor rotational sped, which corresponds to the 100% flow
command.
• A3-02: System oil pressure.
Set the system maximum pressure.
• A3-03: Max. oil pressure.
Set the pressure span of the pressure transducer (corresponding to the output pressure