MD500 User Manual 7. Description of Parameters
- 147 -
The related parameters are described as follows:
Function Code Parameter Name Setting Range Default
F1-00 Motor type selection 0: Common asynchronous motor
1: Variable frequency asynchronous motor
1
F1-01 Rated motor power 0.1 to 1000.0 kW Model
dependent
F1-02 Rated motor voltage 1 to 2000 V Model
dependent
F1-03 Rated motor current WR$$&GULYHSRZHUN:
0.1 to 6553.5 A (AC drive power > 55 kW)
Model
dependent
F1-04 Rated motor frequency 0.01 Hz to max. frequency Model
dependent
F1-05 Rated motor speed 1 to 65535 RPM Model
dependent
F1-00 to F1-05 are motor nameplate parameters. Set them correctly according to the motor nameplate to ensure accurate motor
DXWRWXQLQJUHVXOW7KHDGYDQWDJHVRI9)RUYHFWRUFRQWUROFDQEHREWDLQHGRQO\DIWHUFRUUHFWPRWRUSDUDPHWHUVDUHDSSOLHG
Function Code Parameter Name Setting Range Default
F1-06 Stator resistance WRȎ$&GULYHSRZHUN:
WRȎ$&GULYHSRZHU!N:
Model
dependent
F1-07 Rotor resistance WRȎ$&GULYHSRZHUN:
WRȎ$&GULYHSRZHU!N:
Model
dependent
F1-08 Leakage inductive reactance WRP+$&GULYHSRZHUN:
0.001 to 65.535 mH (AC drive power > 55 kW)
Model
dependent
) Mutual inductive reactance WRP+$&GULYHSRZHUN:
0.01 to 655.35 mH (AC drive power > 55 kW)
Model
dependent
F1-10 No-load current WR)$&GULYHSRZHUN:
0.1 to F1-03 (AC drive power > 55 kW)
Model
dependent
F1-06 to F1-10: These function parameters are obtained by means of motor auto-tuning. Each time F1-01 (Rated motor power) or
)5DWHGPRWRUYROWDJHLVPRGLÀHGWKH$&GULYHDXWRPDWLFDOO\UHVWRUHV)WR)WRFRPPRQVWDQGDUG<VHULHVPRWRU
parameters.
If motor auto-tuning cannot be performed on site, set these parameters according to the data provided by motor manufacturer.
Function Code Parameter Name Setting Range Default
F1-27 Encoder pulses per revolution 1 to 65535 1024
F1-27 sets pulses per revolution (PPR) of the encoder. In the CLVC control mode, F1-27 must be set correctly. Otherwise, the motor
cannot run properly.