The MD500 provides a digital output (DO) terminal, an analog output (AO) terminal, a relay terminal and an FM terminal (either
high-speed pulse output or open-collector output).
([WUD$2WHUPLQDO$2UHOD\WHUPLQDOUHOD\DQG'2WHUPLQDO'2DUHSURYLGHGE\WKH,2H[WHQVLRQFDUG
Function Code Parameter Name Setting Range Default
F5-00 FM terminal output mode
0: Pulse output (FMP)
1: Digital output (FMR)
0
This function parameter is a programmable multiplexing terminal and determines whether the FM terminal is high-speed pulse
output (FMP) or open-collector output (FMR). When used for high-speed pulse output, the max. output frequency is 100 kHz. For
details, see the description of F5-06.
Function Code Parameter Name Setting Range Default
F5-01 FMR function selection
0 to 41
0
F5-02 5HOD\7$7%7&
function selection
0 to 41
2
F5-03 ([WHQVLRQFDUGUHOD\3$3
%3&IXQFWLRQVHOHFWLRQ
0 to 41
0
F5-04 DO1 function selection
0 to 41
1
F5-05 Extension card DO2
function selection
0 to 41
4
7KHVHÀYHIXQFWLRQSDUDPHWHUVVHOHFWWKHIXQFWLRQRIWKHÀYHGLJLWDORXWSXWWHUPLQDOV7$7%7&LVWKHUHOD\RIWKH0'DQG3
$3%3&LVWKHUHOD\RQWKH,2H[WHQVLRQFDUG
7KHIXQFWLRQVRIWKHGLJLWDORXWSXWWHUPLQDOVDUHGHVFULEHGLQWKHIROORZLQJÀJXUH
Value Function Description
0 No output
The terminal has no function.
1 AC drive running
When the AC drive is running and has output frequency (can be zero),
the terminal set for this function becomes on.
2 Fault output
When a fault occurs and the AC drive stops due to the fault, the terminal
set for this function becomes on.
3 Frequency level detection 1 output
5HIHUWRWKHGHVFULSWLRQVRI)DQG)
4 Frequency reached
Refer to the descriptions of F8-21.
5 Zero-speed running (no
output at stop)
When the output frequency is 0 during drive running, the terminal
set for this function becomes on. When the drive stops, the terminal
becomes off.
6 Motor overload pending
7KH$&GULYHMXGJHVWKHPRWRURYHUORDGSHQGLQJDFFRUGLQJWRWKH
pending threshold before performing overload protection. If the pending
threshold is exceeded, the terminal set for this function becomes on.
)RUPRWRURYHUORDGSDUDPHWHUVVHHWKHGHVFULSWLRQVRI)WR)
7 AC drive overload pending
The terminal set for this function becomes on 10s before the AC drive
performs overload protection.
8 Set count value reached
The terminal set for this function becomes on when the count value
reaches the value set in Fb-08.
Designated count value reached
The terminal set for this function becomes on when the count value
UHDFKHVWKHYDOXHVHWLQ)E
10 Length reached
The terminal set for this function becomes on when the detected actual
length exceeds the value set in Fb-05.
11 PLC cycle completed
The terminal set for this function outputs a pulse signal with width of
250 ms when simple PLC completes one cycle.