MD500 User Manual 7. Description of Parameters
)XQFWLRQRIWKH9'27HUPLQDOV
The VDO terminals have the same digital output functions (1 to 41) as the DO terminals do. The VDO can be used together with
VDIx to implement some simple logic control.
Function Code Parameter Name Setting Range Default
A1-11 VDO1 function selection 0: Short with physical DIx internally
1 to 40
0
A1-12 VDO2 function selection 0: Short with physical DIx internally
1 to 40
0
A1-13 VDO3 function selection 0: Short with physical DIx internally
1 to 40
0
A1-14 VDO4 function selection 0: Short with physical DIx internally
1 to 40
0
A1-15 VDO5 function selection 0: Short with physical DIx internally
1 to 40
0
A1-16 VDO1 output delay 0.0s to 3600.0s 0.0s
A1-17 VDO2 output delay 0.0s to 3600.0s 0.0s
A1-18 VDO3 output delay 0.0s to 3600.0s 0.0s
$ VDO4 output delay 0.0s to 3600.0s 0.0s
A1-20 VDO5 output delay 0.0s to 3600.0s 0.0s
A1-10 VDO active mode selection 0: High level active
1: Low level active
00000
Unit's digit: VDO1
Ten's digit: VDO2
Hundred's digit: VDO3
Thousand's digit: VDO4
Ten’s thousand's digit: VDO5
)XQFWLRQRIWKH$,7HUPLQDOV
7KH0'SURYLGHVWZR$,WHUPLQDOV$,$,$QH[WUD$,WHUPLQDO$,LVSURYLGHGE\WKH,2H[WHQVLRQFDUG
Here use the AI terminals as DI. When the AI input voltage is higher than 7 V, the AI is in the high level state. When the AI input
voltage is lower than 3 V, the AI is in the low level state. The AI is in the hysteresis state between 3 V and 7 V.
)LJXUH5HODWLRQVKLSEHWZHHQWKH$,LQSXWYROWDJHDQGWKH',VWDWH
AI voltage
7 VDC
3 VDC
DI state
Time
OFF
ON ON