MD500 User Manual 7. Description of Parameters
- 201 -
Note
The max. value in the range indicates Xmax in the following formulas to
FDOFXODWHWKH$2JDLQDQGWKH$2]HURRIIVHWFRHIÀFLHQW
Function Code Parameter Name Setting Range Default
) Max. FMP output frequency 0.01 to 100.00 kHz 50.00 kHz
This function parameter sets the maximum pulse output frequency when the FM terminal is used for pulse output.
Function Code Parameter Name Setting Range Default
F5-10 $2]HURRIIVHWFRHIÀFLHQW -100.0% to 100.0% 0.0%
F5-11 AO1 gain -10.00 to 10.00 1.00
F5-12 $2]HURRIIVHWFRHIÀFLHQW -100.0% to 100.0% 0.00%
F5-13 AO2 gain -10.00 to 10.00 1.00
F5-23 AO1 output signal selection 0: Voltage signal
1: Current signal
0
These four function parameters generally correct the zero offset of analog output and the output amplitude error. They can also
GHÀQHWKHUHTXLUHG$2FXUYH
7KH]HURRIIVHWFRHIÀFLHQWRI$2DQG$2FRUUHVSRQGVWR9RUP$<RXFDQFDOFXODWHWKHJDLQDQGWKH]HURRIIVHW
FRHIÀFLHQWIURPWKHIROORZLQJIRUPXODV
K =
(Y1 Y2) x Xmax
(X1 X2) x Ymax
b =
(X1 xY2 X2 x Y1)
(X1 X2) x Ymax
In the formulas:
ƕ "b" represents the zero offset.
ƕ "k" represents the gain.
ƕ "X" represents the output frequency.
ƕ "Y" represents the actual output of the AO.
ƕ " Xmax " represents the max. output frequency (determined by F0-10).
ƕ "Ymax" represents the max. output 10 V or 20 mA.
For example, the AO is used for output of frequency reference. To implement output of 8 V (Y1) at 0 Hz (x1) and output of 4 V (Y2)
DW+];DFFRUGLQJWRWKHIRUPXODV\RXFDQREWDLQWKHJDLQDQGWKH]HURRIIVHWFRHIÀFLHQWDVIROORZV
K =
(8 4) x 50
(0 40) x 10
=
0.5
b =
(0 x 4 - 40 x 8)
(0 - 40) x 10
= 80%
Then you can set F5-11 to -0.5 and set F5-10 to 80%.
The AO output signal type and corresponding max. value are as follows:
AO1 output signal Corresponding Max. Output (Ymax)
Voltage 10 V
Current 20 mA