MD500 User Manual 7. Description of Parameters
- 213 -
Function Code Parameter Name Setting Range Default
) Frequency detection value 1 0.00 Hz to max. frequency 50.00 Hz
F8-20 Frequency detection hysteresis 1 0.0% to 100.0% 5.0%
F8-28 Frequency detection value 2 0.00 Hz to max. frequency 50.00 Hz
) Frequency detection hysteresis 2 0.0% to 100.0% 5.0%
),WVHWVWKHGHWHFWLRQYDOXHIRUWKHGLJLWDORXWSXWIXQFWLRQ:KHQWKHGULYHUXQQLQJIUHTXHQF\H[FHHGVWKHGHWHFWLRQYDOXH
the digital output terminal set for function 3 becomes on.
),WVHWVWKHK\VWHUHVLVOHYHOIRUWKHIUHTXHQF\GHWHFWLRQIXQFWLRQ,WLVDSHUFHQWDJHRIWKHIUHTXHQF\GHWHFWLRQYDOXH)
7.11.5 Frequency Reference Reached Detection Width
This function sets the detection width of the frequency reference.
Figure 7-65 Frequency reached detection width
Detection width =
max. frequency x F8-21
Time (t)
Output
frequency (Hz)
Frequency
reference
ON ON
Frequency
reached signal
Function Code Parameter Name Setting Range Default
F8-21 Detection width of target frequency
reached
0.00 to 100% 0.0%