3. Electrical Installation MD500 User Manual
- 46 -
3.2.2 Wiring Precautions
Ƶ
Cable Selection
Inovance recommends symmetrical shielded cable as main circuit cable, which can reduce electromagnetic radiation of the
entire conductive system compared with the four-conductor cable.
PE
PE conductor
and shield
Shield Shield
PE
PE
Shield
Ƶ
Power Input
ƕ There are no phase sequence requirements for three-phase cable connections. It does not matter which phase connects
to each of the R, S and T terminals.
ƕ 7KHFDEOHVSHFLÀFDWLRQDQGLQVWDOODWLRQRIDOOH[WHUQDOSRZHUFDEOHVPXVWFRPSO\ZLWKORFDOVDIHW\UHJXODWLRQVDQGUHOHYDQW
IEC standards.
ƕ Use power cables that have copper conductors of the proper size.
ƕ ,QVWDOOWKHÀOWHUFORVHWRWKHSRZHULQSXWVLGHRIWKH$&GULYHZLWKWKHFRQQHFWLQJFDEOHVKRUWHUWKDQFP&RQQHFWWKH
JURXQGWHUPLQDORIWKHÀOWHUDQGWKHJURXQGWHUPLQDORIWKHGULYHWRJHWKHU0DNHVXUHWRLQVWDOOWKHÀOWHUDQGWKHGULYHRQ
the same conductive surface and connect this surface to the main ground terminal of the cabinet.
Conductive mounting surface