MD500 User Manual 5. Quick Setup
- 73 -
CONTINUE Para. Parameter name Default Commission
Select frequency reference source F0-03 Main frequency source X selection 0
If F0-08 is frequency reference
0:Digital setting F0-08 (pressing
or can revise F0-08 easily,
and the revised value won’t be cleared even after power off)
1:Digital setting F0-08 (pressing
or can change F0-08
easily, but the revised value would be cleared after power off)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference setting
7: Simple PLC
8: PID
&RPPXQLFDWLRQVHWWLQJ
Set F0-08
F0-08 Preset frequency 50.00
If AI1 is frequency reference
Hz to F0-10
Set AI1
F4-13 AI curve 1 minimum input 0.00
If AI2 is frequency reference
0 V to F4-15;
F4-14 Corresponding setting of AI1 minimum input 0.0
-100.0% to 100.0%
F4-15 AI1 maximum input 10.00
F4-13 to 10.00 V
F4-16 Corresponding setting of AI1 maximum input 100.0
-100.0% to 100.0%
Set AI2
F4-18 AI curve 2 minimum input 0.00
0 V to F4-20;
) Corresponding setting of AI2 minimum input 0.0
-100.0% to 100.0%
F4-20 AI2 maximum input 10.00
F4-18 to 10.00 V
F4-21 Corresponding setting of AI2 maximum input 100.0
-100.0% to 100.0%
CONTINUE Para. Parameter name Default Commission