MD500 User Manual 5. Quick Setup
- 77 -
CONTINUE Para. Parameter name Default Commissioning
If any digital output is used
Set DO function
F5-00 FM output mode selection 0
0: FM terminal outputs pulses, the frequency of which represents
the value of variable which is assigned by F5-06.
1: FM terminal outputs switch signal, the value of which
represents the status of variable which is assigned by F5-01
F5-01 FM (switch signal) function selection 0
0: No output
1: AC Drive running
2: Fault output
3: Frequency-level detection FDT1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
'HVLJQDWHGFRXQWYDOXHUHDFKHG
10: Length reached
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for RUN
16: Reserved
17: Frequency upper limit reached
18: Frequency lower limit reached (no output at stop)
8QGHUYROWDJHVWDWXVRXWSXW
20: Communication setting
21,22: Reserved
23: Zero-speed running 2 (having output at stop)
24: Accumulative power-on time reached
25: Frequency level detection FDT2 output
CONTINUE Para. Parameter name Default Commissioning