6. Parameter Table MD500 User Manual
Function Code Parameter Name Setting Range Default Property
FP-04 Selection of parameter
PRGLÀFDWLRQ
0, 1 0
ƿ
Group A0: Torque Control and Limit
A0-00 6SHHG7RUTXHFRQWUROVHOHFWLRQ 0, 1 0
ƾ
A0-01 Torque reference source
in torque control
0 to 7 0
ƾ
A0-03 Torque digital setting
in torque control
-200.0% to 200.0% 150.0%
ƿ
A0-05 Forward max. frequency
in torque control
0.00 Hz to max. frequency (F0-10) 50.00 Hz
ƿ
A0-06 Reverse max. frequency
in torque control
0.00 Hz to max. frequency (F0-10) 50.00 Hz
ƿ
A0-07 Acceleration time in
torque control
0.00s to 650.00s 0.00s
ƿ
A0-08 Deceleration time in
torque control
0.00s to 650.00s 0.00s
ƿ
*URXS$9LUWXDO','2
A1-00 VDI1 function selection WR 0
ƾ
A1-01 VDI2 function selection WR 0
ƾ
A1-02 VDI3 function selection WR 0
ƾ
A1-03 VDI4 function selection WR 0
ƾ
A1-04 VDI5 function selection WR 0
ƾ
A1-05 VDI active state setting mode 00000 to 11111 00000
ƾ
A1-06 Selection of VDI active state 00000 to 11111 00000
ƾ
A1-07 Function selection for
AI1 used as DI
WR 0
ƾ
A1-08 Function selection for
AI2 used as DI
WR 0
ƾ
$ Function selection for
AI3 used as DI
WR 0
ƾ
A1-10 Active state selection
for AI used as DI
000 to 111 000
ƿ
A1-11 VDO1 function selection 0 to 41 0
ƿ
A1-12 VDO2 function selection 0 to 41 0
ƿ
A1-13 VDO3 function selection 0 to 41 0
ƿ
A1-14 VDO4 function selection 0 to 41 0
ƿ
A1-15 VDO5 function selection 0 to 41 0
ƿ
A1-16 VDO1 output delay 0.0s to 3600.0s 0.0s
ƿ
A1-17 VDO2 output delay 0.0s to 3600.0s 0.0s
ƿ
A1-18 VDO3 output delay 0.0s to 3600.0s 0.0s
ƿ
$ VDO4 output delay 0.0s to 3600.0s 0.0s
ƿ
A1-20 VDO5 output delay 0.0s to 3600.0s 0.0s
ƿ
A1-21 VDO active mode selection 00000 to 11111 00000
ƿ
Group A2: Motor 2 Parameters
A2-00 Motor type selection 0 to 1 0
ƾ
A2-01 Rated motor power 0.1 to 30.0 kW Model
dependent
ƾ
A2-02 Rated motor voltage 1 to 1000 V Model
dependent
ƾ
A1-03 Rated motor current
WR$$&GULYHSRZHUN:
0.1 to 6553.5 A (AC drive power > 55 kW)
Model
dependent
ƾ