Installation
3-140-UM-EN-02
23 / 56
5.3 Electrical installation
DANGER
Electric shock
Touching energized system parts can cause immediate death or serious injury.
u Make sure that installation work is only carried out by authorized specialists.
u Before carrying out any work on the system, disconnect the power supply and check that
no voltage is present.
u If an insulation is damaged, disconnect the power supply immediately and arrange for im-
mediate repair.
The device is equipped with screw terminal connectors. Stripped rigid conductors or flexible conductors with
crimped ferrules (AEH) can be plugged directly into the screw terminal
Connectable conductors:
l Wire range (rigid or flexible): 1.0…2.5mm
2
l Stripping length: 6-7mm
l AWG 28-12
The functionality of different connections depends on the installed modules and the activated options.