EasyManuals Logo

IntelliSAW CAM-5 User Manual

IntelliSAW CAM-5
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
User Manual
910.00382.0001 May 2018
54
7.1.2 MODBUS REGISTERS
Register
Description
Type
Min
Max
Scale
Error Code
418
5
temp 1
signed 16
-500
1675
0.1 C
0x8000
419
temp 2
signed 16
-500
1675
0.1 C
0x8000
420
temp 3
signed 16
-500
1675
0.1 C
0x8000
421
temp 4
signed 16
-500
1675
0.1 C
0x8000
422
temp 5
signed 16
-500
1675
0.1 C
0x8000
423
temp 6
signed 16
-500
1675
0.1 C
0x8000
424
temp 7
signed 16
-500
1675
0.1 C
0x8000
425
temp 8
signed 16
-500
1675
0.1 C
0x8000
426
temp 9
signed 16
-500
1675
0.1 C
0x8000
427
temp 10
signed 16
-500
1675
0.1 C
0x8000
428
temp 11
signed 16
-500
1675
0.1 C
0x8000
429
temp 12
signed 16
-500
1675
0.1 C
0x8000
430
ambient 1
signed 16
-400
1250
0.1 C
0x8000
431
RH 1
unsigned 16
6
0
1000
0.1% RH
0xFFFF
432
ambient 2
signed 16
-400
1250
0.1 C
0x8000
433
RH 2
unsigned 16
0
1000
0.1% RH
0xFFFF
434
ambient 3
signed 16
-400
1250
0.1 C
0x8000
435
RH 3
unsigned 16
0
1000
0.1% RH
0xFFFF
436
ambient 4
signed 16
-400
1250
0.1 C
0x8000
437
RH 4
unsigned 16
0
1000
0.1% RH
0xFFFF
438
ambient 5
signed 16
-400
1250
0.1 C
0x8000
439
RH 5
unsigned 16
0
1000
0.1% RH
0xFFFF
440
ambient 6
signed 16
-400
1250
0.1 C
0x8000
441
RH 6
unsigned 16
0
1000
0.1% RH
0xFFFF
442
ambient 7
signed 16
-400
1250
0.1 C
0x8000
443
RH 7
unsigned 16
0
1000
0.1% RH
0xFFFF
444
ambient 8
signed 16
-400
1250
0.1 C
0x8000
445
RH 8
unsigned 16
0
1000
0.1% RH
0xFFFF
446
SD1 Total
unsigned 16
0
65534
10 "pC"
7
0xFFFF
447
SD2 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
448
SD3 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
449
SD4 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
450
PD1 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
451
PD2 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
452
PD3 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
453
PD4 Total
unsigned 16
0
65534
10 "pC"
0xFFFF
454
Data version = 1
unsigned 16
0
65534
na
0xFFFF
455
noise 1
unsigned 16
0
65534
10 "pC"
0xFFFF
5
Registers start at 0. 418 is 400418 or 0x01A2 in the datagram.
6
RH may be treated as signed 16 making the error code translate to a small negative number.
7
Partial discharge and surface discharge are nonlinear, and the scale is approximate.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IntelliSAW CAM-5 and is the answer not in the manual?

IntelliSAW CAM-5 Specifications

General IconGeneral
BrandIntelliSAW
ModelCAM-5
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals