OptidriveODP‐2UserGuideRevision1.30
www.invertekdrives.com
35
7 DigitalInputFunctions
The“SelectedSpeedReference”referredtointheabovetableisdeterminedbythevaluesetinP1‐12(ControlMode):
P1‐12(controlMode) SelectedSpeedReference
0:TerminalMode Analoginput1
1:KeypadMode(uni‐directional) DigitalPotentiometer
2:KeypadMode(bi‐directional) DigitalPotentiometer
3:UserPIDmode PIDcontrolleroutput
4:FieldbusControl SpeedreferenceviaFieldbus
5:SlaveMode SpeedreferenceviaOptibus
Note
1) ToaccessP8‐11,setP1‐14=201
2) Ifamotorthermistor(PTCtypeonly,ornormallyclosedthermalswitchcontact)istobeconnected,thismustbeselectedinP2‐33.
Connectthethermistorbetweenterminal1andterminal10.
3) WhenP1‐12=0andP1‐13=10or20
,theMotorisedPot/KeypadreferenceisautomaticallyselectedtobetheSelectedSpeed
Reference