OptidriveODP‐2UserGuideRevision1.30
www.invertekdrives.com
43
8 ExtendedParameters
8.5. ParameterGroup0–MonitoringParameters(ReadOnly)
Par Description Units
P0‐01 AnalogInput1AppliedSignalLevel %
Displaysthesignallevelappliedtoanaloginput1(Terminal6)afterscalingandoffsetshavebeenapplied.
P0‐02 AnalogInput2AppliedSignalLevel %
Displaysthesignallevelappliedtoanaloginput2(Terminal10)afterscalingandoffsetshavebeenapplied.
P0‐03 DigitalInputStatus ‐
Displaysthestatusofthedriveinputs,startingwiththelefthandsidedigit=DigitalInput1etc.
P0‐04 PreRampSpeedControllerReference Hz
Displaysthesetpointreferenceinputappliedtothedriveinternalspeedcontroller
P0‐05 TorqueControllerReference %
Displaysthesetpointreferenceinputappliedtothedriveinternaltorquecontroller
P0‐06 DigitalSpeedReference(MotorisedPot) Hz
DisplaysthevalueofthedriveinternalMotorisedPot(usedforkeypad)speedreference
P0‐07 FieldbusCommunicationSpeedReference Hz
DisplaysthesetpointbeingreceivedbythedrivefromthecurrentlyactiveFieldbusinterface.
P0‐08 PIDReference(Setpoint) %
DisplaysthesetpointinputtothePIDcontroller.
P0‐09 PIDFeedbackLevel %
DisplaystheFeedbackinputsignaltothePIDcontroller
P0‐10 PIDControllerOutput %
DisplaystheoutputlevelofthePIDcontroller
P0‐11 AppliedMotorVoltage V
Displaystheinstantaneousoutputvoltagefromthedrivetothemotor
P0‐12 OutputTorque %
Displaystheinstantaneousoutputtorquelevelproducedbythemotor
P0‐13 TripHistoryLog ‐
Displaysthelastfourfaultcodesforthedrive.Refertosection11.1 forfurtherinformation
P0‐14 MotorMagnetisingCurrent(Id) A
DisplaysthemotormagnetisingCurrent,providinganautotunehasbeensuccessfullycompleted.
P0‐15 MotorRotorCurrent(Iq) A
DisplaysthemotorRotor(torqueproducing)current,providinganautotunehasbeensuccessfullycompleted.
P0‐16 DCBusVoltageRippleLevel V
DisplaysthelevelofripplepresentontheDCBusVoltage.ThisparameterisusedbytheOptidriveforvariousinternalprotection
andmonitoringfunctions.
P0‐17 MotorStatorresistance(Rs) Ω
Displaysthemeasuredmotorstatorresistance,providinganautotunehasbeensuccessfullycompleted.
P0‐18 MotorStatorInductance(Ls) H
Displaysthemeasuredmotorstatorinductance,providinganautotunehasbeensuccessfullycompleted.
P0‐19 MotorRotorResistance(Rr) Ohms
Displaysthemeasuredmotorrotorresistance,providinganautotunehasbeensuccessfullycompleted.
P0‐20 DCBusVoltage V
DisplaystheinstantaneousDCBusVoltageinternallywithinthedrive
P0‐21 DriveTemperature °C
DisplaystheInstantaneousHeatsinkTemperaturemeasuredbythedrive
P0‐22 TimeRemainingtonextservice V
Displaysthenumberofhoursremainingontheservicetimecounterbeforethenextserviceisdue.
P0‐23 OperatingTimeAccumulatedWithHeatsinkTemperatureAbove80°C HH:MM:SS
DisplaystheamountoftimeinhoursandminutesthattheOptidrivehasoperatedforduringitslifetimewithaheatsink
temperatureinexcessof80°C.ThisparameterisusedbytheOptidriveforvariousinternalprotectionandmonitoringfunctions.
P0‐24 OperatingTimeAccumulatedWithAmbientTemperatureAbove80°C HH:MM:SS
DisplaystheamountoftimeinhoursandminutesthattheOptidrivehasoperatedforduringitslifetimewithanambient
temperatureinexcessof80°C.ThisparameterisusedbytheOptidriveforvariousinternalprotectionandmonitoringfunctions.
P0‐25 RotorSpeed(EstimatedorMeasured) ‐
InVectorcontrolmode,thisparameterdisplayseithertheestimatedrotorspeedofthemotor,ifnoencoderfeedbackis
present,orthemeasuredrotorspeedifanoptionalEncoderFeedbackInterfaceOptionisfitted.
P0‐26 EnergyConsumptionkWhMeter kWh
DisplaystheamountofenergyconsumedbythedriveinkWh.Whenthevaluereaches1000,itisresetbackto0.0,andthevalue
ofP0‐27(*MWhmeter)isincreased.
P0‐27 EnergyConsumptionMWhMeter MWh
DisplaystheamountofenergyconsumedbythedriveinMWh.
P0‐28 SoftwareVersionandChecksum ‐
Displaysthesoftwareversionofthedrive
P0‐29 DriveType ‐
Displaysthetypedetailsofthedrive
P0‐30 DriveSerialNumber ‐
Displaystheuniqueserialnumberofthedrive.