OptidriveODP‐2UserGuideRevision1.30
www.invertekdrives.com
49
10 TechnicalData
10.2.5. 500–600Volt(+/‐10%),3PhaseInput,3PhaseOutput
Power
Rating
Nominal
Input
Current
Fuseor
MCB(TypeB)
Supply
Cable
Size
Rated
Output
Current
Motor
Cable
Size
Maximum
Motor
CableLength
Recommended
Brake
Resistance
kW HP A NonUL UL mm AWG/
kcmil
A mm AWG m ftΩ
0.75 1 2.5 10 6 1.5 14 2.1 1.5 14 100 330 600
1.5 2 3.7 10 6 1.5 14 3.1 1.5 14 100 330 300
2.2 3 4.9 10 10 1.5 14 4.1 1.5 14 100 330 200
4 5 7.8 10 10 1.5 14 6.5 1.5 14 100 330 150
5.5 7.5 10.8 16 15 2.5 14 9 1.5 14 100 330 100
7.5 10 14.4 20 20 4 12 12 1.5 14 100 330 80
11 15 20.6 32 30 6 10 17 2.5 10 100 330 50
15 20 26.7 40 35 10 8 22 4 10 100 330 33
18.5 25 34 50 45 16 8 28 6 8 100 330 33
22 30 41.2 63 60 16 6 34 6 8 100 330 22
30 40 49.5 63 70 16 6 43 10 6 100 330 16
37 50 62.2 80 80 25 4 54 16 4 100 330 16
45 60 75.8 100 100 35 3 65 25 4 100 330 12
55 75 90.9 125 125 50 2 78 25 3 100 330 12
75 100 108.2 160 150 70 1/0 105 50 1/0 100 330 8
90 125 127.7 160 175 70 2/0 130 70 2/0 100 330 8
110 175 134.8 200 175 95 2/0 150 70 3/0 100 330 8
10.3. AdditionalInformationforULApprovedInstallations
OptidriveP2isdesignedtomeettheULrequirements.Inordertoensurefullcompliance,thefollowingmustbefullyobserved.
InputPowerSupplyRequirements
SupplyVoltage 200
240RMSVoltsfor230Voltratedunits,+/‐ 10%variationallowed.240VoltRMSMaximum
380–480Voltsfor400Voltratedunits,+/‐10%variationallowed,Maximum500VoltsRMS
500–600Voltsfor600Voltratedunits,+/‐10%variationallowed,Maximum600VoltsRMS
Imbalance Maximum3%voltagevariationbetweenphase
phasevoltagesallowed
AllOptidriveP2unitshavephaseimbalancemonitoring.Aphaseimbalanceof>3%willresultinthedrivetripping.
Forinputsupplieswhichhavesupplyimbalancegreaterthan3%(typicallytheIndiansub‐continent&partsofAsia
PacificincludingChina)InvertekDrivesrecommendstheinstallationofinputlinereactors.Al
ternatively,thedrives
canbeoperatedasasinglephasesupplydrivewith50%derating.
Frequency 50–60Hz+/‐5%Variation
ShortCircuitCapacity VoltageRating MinkW(HP) MaxkW(HP) Maximumsupplyshort‐circuitcurrent
All All All 100kArms(AC)
Allthedrivesintheabovetablearesuitableforuseonacircuitcapableofdeliveringnotmorethantheabove
specifiedmaximumshort‐circuitAmperessymmetricalwiththespecifiedmaximumsupplyvoltage.
Incomingpowersupplyconnectionmustbeaccordingtosection4.3
AllOptidriveP2unitsareintendedforindoorinstallationwithincontrolledenvironmentswhichmeettheconditionlimitsshowninsection
10.1
Branchcircuitprotectionmustbeinstalledaccordingtotherelevantnationalcodes.Fuseratingsandtypesareshowninsection10.2
SuitablePowerandmotorcablesshouldbeselectedaccordingtothedata showninsection10.2
Powercableconnectionsandtighteningtorquesareshowninsection3.4
OptidriveP2providesmotoroverloadprotectioninaccordancewiththeNationalElectricalCode(US).
• Whereamotorthermistorisnotfitted,ornotutilised,ThermalOverloadMemoryRetentionmustbeenabledbysettingP4‐12=1
• Whereamotorthermistorisfittedandconnectedtothedrive,connectionmustbecarrie
doutaccordingtotheinformation
showninsection4.7