10 TechnicalData
10. TechnicalData
10.1. Environmental
Ambienttemperaturerange:Operational :‐10…50°CIP20Units
:‐10…40°CIP55Units(ULApproved)
:‐10…50°CIP55Units(NonULApprovedwithderating,refertosection10.4.1for
DeratingforAmbientTemperatureInformation)
‐10…40°CIP66Units(ULApproved)
:‐10…50°CIP
66Units(NonULApprovedwithderating,refertosection10.4.1for
DeratingforAmbientTemperatureInformation)
StorageandTransportation :‐40°C…60°C
Maxaltitudeforratedoperation :1000m(Refertosection10.4.2forDeratingforAltitudeInformation)
RelativeHumidity :<95%(noncondensing)
No
te : DrivemustbeFrostandmoisturefreeatalltimes
Installationabove2000misnotULapproved
10.2. Input/OutputPowerandCurrentratings
ThefollowingtablesprovidetheoutputcurrentratinginformationforthevariousOptidriveP2models.InvertekDrivesalwaysrecommendthat
selectionofthecorrectOptidriveisbaseduponthemotorfullloadcurrentattheincomingsupplyvoltage.
10.2.1. 200–240Volt(+/‐10%),1PhaseInput,3PhaseOutput
Power
Rating
Nominal
Input
Current
Fuseor
MCB(TypeB)
Supply
Cable
Size
Rated
Output
Current
Motor
Cable
Size
Maximum
Motor
CableLength
Recommended
Brake
Resistance
kW HP A NonUL UL mm AWG/
kcmil
A mm AWG m ftΩ
0.75 1 8.5 16 15 2.5 14 4.3 1.5 14 100 330 100
1.5 1.5 15.2 20 20 4 12 7 1.5 14 100 330 50
2.2 1.5 19.5 25 25 4 10 10.5 1.5 14 100 330 35
Note
• Ratingsshownaboveapplyto40°CAmbienttemperature.Forderatinginformation,refertosection10.4.1
• Themaximummotorcablelengthstatedappliestousingashieldedmotorcable.Whenusinganunshieldedcable,themaximumcable
lengthlimitmaybeincreasedby50%.WhenusingtheInvertekDrivesrecommendedou
tputchoke,themaximumcablelengthmaybe
increasedby100%
• ThePWMoutputswitchingfromanyinverterwhenusedwithalongmotorcablelengthcancauseanincreaseinthevoltageatthemotor
terminals,dependingonthemotorcablelengthandinductance.Therisetimeandpeakvolta
gecanaffecttheservicelifeofthemotor.
InvertekDrivesrecommendusinganoutputchokeformotorcablelengthsof50mormoretoensuregoodmotorservicelife
• ForULcompliantinstallation,useCopperwirewithaminimuminsulationtemperatureratingof70°C,ULClassCCorCl
assJFuses
10.2.2. 200–240Volt(+/‐10%),3PhaseInput,3PhaseOutput
Power
Rating
Nominal
Input
Current
Fuseor
MCB(TypeB)
Supply
Cable
Size
Rated
Output
Current
Motor
Cable
Size
Maximum
Motor
CableLength
Recommended
Brake
Resistance
kW HP A NonUL UL mm AWG/kcmil A mm AWG m ftΩ
0.75 1 5.1 10 10 1.5 14 4.3 1.5 14 100 330 100
1.5 2 8.3 16 15 2.5 14 7 1.5 14 100 330 50
2.2 3 12.6 16 17.5 2.5 12 10.5 1.5 14 100 330 35
4 5 21.6 32 30 6 10 18 2.5 10 100 330 20
5.5 7.5 29.1 40 40 10 8 24 4 10 100 330 20
7.5 10 36.4 50 50 16 8 30 6 8 100 330 22
11 15 55.8 80 70 25 4 46 10 6 100 330 22
15 20 70.2 100 90 35 3 61 16 4 100 330 12
18.5 25 82.9 125 110 50 2 72 25 3 100 330 12
22 30 103.6 160 150 70 1 90 35 2 100 330 6
30 40 126.7 160 175 70 2/0 110 50 1/0 100 330 6
37 50 172.7 250 225 120 4/0 150 70 3/0 100 330 6
45 50 183.3 250 250 120 4/0 180 95 4/0 100 330 6
55 50 205.7 300 300 185 300 202 120 250 100 330 6
75 50 255.5 400 350 2x95 400 248 150 350 100 330 6
Note
• Ratingsshownaboveapplyto40°CAmbienttemperature.Forderatinginformation,refertosection10.4.1
• Operationwithsinglephasesupplyispossible,with50%deratingoftheoutputcurrentcapacity
• Themaximummotorcablelengthstatedappliestousingashieldedmotorcable.Whenusinganunshieldedcable,th
emaximumcable
lengthlimitmaybeincreasedby50%.WhenusingtheInvertekDrivesrecommendedoutputchoke,themaximumcablelengthmaybe
increasedby100%
• ThePWMoutputswitchingfromanyinverterwhenusedwithalongmotorcablelengthcancauseanincreaseinthevoltageatth
emotor
terminals,dependingonthemotorcablelengthandinductance.Therisetimeandpeakvoltagecanaffecttheservicelifeofthemotor.
InvertekDrivesrecommendusinganoutputchokeformotorcablelengthsof50mormoretoensuregoodmotor servicelife
• ForULcompliantinsta
llation,useCopperwirewithaminimuminsulationtemperatureratingof70°C,ULClassCCorClassJFuses