8ExtendedParameters
Par Description Units
P0‐31 DriveLifetimeOperatingTime HH:MM:SS
Displaysthetotaloperatingtimeofthedrive.Thefirstvalueshownisthenumberofhours.PressingtheUpkeywilldisplaythe
minutesandseconds.
P0‐32 DriveRunTimeSinceLastTrip(1) HH:MM:SS
Displaysthetotaloperatingtimeofthedrivesincethelastfaultoccurred.Thefirstvalueshownisthenumberofhours.Pressing
theUpkeywilldisplaytheminutesandseconds.
P0‐33 DriveRuntimeSinceLastTrip(2) HH:MM:SS
Displaysthetotaloperatingtimeofthedrivesincethelastfaultoccurred.Thefirstvalueshownisthenumberofhours.Pressing
theUpkeywilldisplaytheminutesandseconds.
P0‐34 DriveRunTimeSinceLastDisable HH:MM:SS
DisplaysthetotaloperatingtimeofthedrivesincethelastRuncommandwasreceived.Thefirstvalueshownisthenumberof
hours.PressingtheUpkeywilldisplaytheminutesandseconds.
P0‐35 DriveInternalCoolingFanTotalOperatingTime HH:MM:SS
DisplaysthetotaloperatingtimeoftheOptidriveinternalcoolingfans.Thefirstvalueshownisthenumberofhours.Pressing
theUpkeywilldisplaytheminutesandseconds.Thisisusedforscheduledmaintenanceinformation
P0‐36 DCBusVoltageLog(256ms) V
P0‐37 DCBusVoltageRippleLog(20ms) V
P0‐38 HeatsinkTemperatureLog(30s) °C
P0‐39 AmbientTemperatureLog(30s) °C
P0‐40 MotorCurrentLog(256ms) A
Theaboveparametersareusedtostorethehistoryofvariousmeasuredlevelswithinthedriveatvariousregulartimeintervals
priortoatrip.Thevaluesarefrozenwhenafaultoccursandcanbeusedfordiagnosticpurposes–seesectionforfurther
information.
P0‐41 CriticalFaultCounter–OverCurrent ‐
P0‐42 Criticalfaultcounter–OverVoltage ‐
P0‐43 Criticalfaultcounter–UnderVoltage ‐
P0‐44 Criticalfaultcounter–OverTemperature ‐
P0‐45 Criticalfaultcounter–BrakeTransistorOverCurrent ‐
P0‐46 Criticalfaultcounter–AmbientOverTemperature ‐
Theseparameterscontainarecordofhowmanytimescertaincriticalfaultshaveoccurredduringadrivesoperatinglifetime.
Thisprovidesusefuldiagnosticdata
P0‐47 Reserved ‐
ReservedParameter
P0‐48 Reserved ‐
ReservedParameter
P0‐49 ModbusRTUCommunicationErrorCounter ‐
ThisparameterisincrementedeverytimeanerroroccursontheModbusRTUcommunicationlink.Thisinformationcanbeused
fordiagnosticpurposes.
P0‐50 CANOpenCommunicationErrorCounter ‐
ThisparameterisincrementedeverytimeanerroroccursontheCANOpencommunicationlink.Thisinformationcanbeused
fordiagnosticpurposes.