OptidriveODP2UserGuideRevision1.30
www.invertekdrives.com
39
8 ExtendedParameters
Par ParameterName Minimum Maximum Default Units
P237 KeypadModeRestartSpeed 0 3 1 ‐
ThisparameterisonlyactivewhenP112=1or2.Whensettings0to3areused,thedrivemustbestartedbypressingtheStartkey
onthekeypad.Whensettings47areused ,thedrivestartingiscontrolledbytheenabledigitalinput.
0:MinimumSpe
ed.Followingastopandrestart,thedrivewillalwaysinitiallyrunattheminimumspeedP102
1:PreviousOperatingSpeed.Followingastopandrestart,thedrivewillreturntothelastkeypadsetpointspeedusedpriorto
stopping
2:CurrentRunningSpeed.WheretheOpt
idriveisconfiguredformultiplespeedreferences(typicallyHand/AutocontrolorLocal/
Remotecontrol),whenswitchedtokeypadmodebyadigitalinput,thedrivewillcontinuetooperateatthelastoperatingspeed
3:PresetSpeed8.Followingastopandrestart,theOptidrivew
illalwaysinitiallyrunatPresetSpeed8(P208)
4:MinimumSpeed(TerminalEnable).Followingastopandrestart,thedrivewillalwaysinitiallyrunattheminimumspeedP102
5:PreviousOperatingSpeed(TerminalEnable).Followingastopandrestart,thedrivewillreturntothela
stkeypadsetpointspeed
usedpriortostopping
6:CurrentRunningSpeed(TerminalEnable).WheretheOptidriveisconfiguredformultiplespeedreferences(typicallyHand/Auto
controlorLocal/Remotecontrol),whenswitchedtokeypadmodebyadigitalinput,thedrivewillcontinuetooperateatth
elast
operatingspeed
7:PresetSpeed8(TerminalEnable).Followingastopandrestart,theOptidrivewillalwaysinitiallyrunatPresetSpeed8(P208)
P238 MainsLossRideThrough/StopControl 0 2 0 ‐
Controlsthebehaviourofthedriveinresponsetoalossofmainspowersupplywhilstthedriveisenabled.
0:MainsLossRideThrough.TheOptidrivewillattempttocontinueoperatingbyrecoveringenergyfromtheloadmotor. Providing
thatthemainslossperiodisshort,andsufficientenergycanbere
coveredbeforethedrivecontrolelectronicspoweroff,thedrive
willautomaticallyrestartonreturnofmainspower
1:CoastToStop.TheOptidrivewillimmediatelydisabletheoutputtothemotor,allowingtheloadtocoastorfreewheel.When
usingthissettingwithhighinertialoads,theSpinSta
rtfunction(P226)mayneedtobeenabled
2:FastRampToStop.Thedrivewillramptostopattherateprogrammedinthe2
nd
decelerationtimeP225
3:DCBusPowerSupplyMode.Thismodeisintendedtobeusedwhenthedriveispowereddirectlyviathe+DCand–DCBus
connections.RefertoyourInvertekSalesPartnerforfurtherdetails.
P239 ParameterAccessLock 0 1 0
0:Unlocked.Allparameterscanbeaccessedandchanged
1:Locked.Parametervaluescanbedisplayed,butcannotbechanged
P240 ExtendedParameterAccessCodeDefinition 0 9999 101 ‐
DefinestheaccesscodewhichmustbeenteredinP114toaccessparametergroupsaboveGroup1