BPD series PV pumping inverter Function parameters
39
0.0–100.0%
If the simulating signal is less than the water-level
threshold and keep in the state after the delay time
set by P15.13, report A-tF and dormant. If the time
is not reached, the signal is bigger than the
water-level threshold; the time will be cleared
automatically. When the signal time is shorter than
the water-level threshold time, the time will be
counted again.
0 is full-water and 1 is no water.
0–10000s
Time setting of full-water delay
Wake-up delay
when full-water
0–10000s
The delay time setting.
During the full-water warning, if the detected
water-level signal is higher than the threshold of
P15.12, the delay counts, after the time set by
P15.14, the warning is cleared. During the
non-continuous application, the delay timing will
clear automatically.
0.0–100.0%
0.0%: Invalid. If it is not 0.0%, when the signal is
longer than P15.15, it will report tSF fault directly
and stop.
Operation time
of water pump
underload
0.0–1000.0s
Set the operation time of underload operation.
Under the continuous underload operation, it will
report A - LL if the operation time is reached.
0.0%: Automatic detection