BPD series PV pumping inverter Function parameters
39
Function
code
Name
Detailed description
Default
Modify
P15.12
Water-level
threshold
0.0100.0%
If the simulating signal is less than the water-level
threshold and keep in the state after the delay time
set by P15.13, report A-tF and dormant. If the time
is not reached, the signal is bigger than the
water-level threshold; the time will be cleared
automatically. When the signal time is shorter than
the water-level threshold time, the time will be
counted again.
0 is full-water and 1 is no water.
25.0%
P15.13
Full-water
delay
010000s
Time setting of full-water delay
5s
P15.14
Wake-up delay
when full-water
010000s
The delay time setting.
During the full-water warning, if the detected
water-level signal is higher than the threshold of
P15.12, the delay counts, after the time set by
P15.14, the warning is cleared. During the
non-continuous application, the delay timing will
clear automatically.
20s
P15.15
Hydraulic
probe damage
0.0100.0%
0.0%: Invalid. If it is not 0.0%, when the signal is
longer than P15.15, it will report tSF fault directly
and stop.
0.0%
P15.16
Operation time
of water pump
underload
0.01000.0s
Set the operation time of underload operation.
Under the continuous underload operation, it will
report A - LL if the operation time is reached.
60.0s
P15.17
Current
0.0%: Automatic detection
50.0%