CHV180 series frequency inverter special for elevator                                Trouble shooting 
.96. 
8.2 Common faults and solutions 
Inverter  may have following faults or  malfunctions during operation, please refer to  the 
following solutions. 
No display after power on: 
  Inspect  whether  the  voltage  of  power  supply  is  the  same  as  the  inverter  rated 
voltage or not with multi-meter. If the power supply has problem, inspect and solve 
it. 
  Inspect  whether  the three-phase  rectify  bridge  is  in  good  condition  or not. If  the 
rectification bridge is burst out, ask for support. 
  Check the CHARGE light. If the light is off, the fault is mainly in the rectify bridge or 
the  buffer  resistor. If the  light  is  on, the fault  may  be  lies  in  the switching  power 
supply. Please ask for support. 
Power supply air switch trips off when power on: 
  Inspect whether the input power supply is grounded or short circuit. Please solve 
the problem. 
  Inspect whether the rectify bridge has been burnt or not. If it is damaged, ask for 
support. 
Motor doesn’t move after inverter running: 
  Inspect  if  there  is  balanced  three-phase  output  among U,  V,  and W. If yes,  then 
motor could be damaged, or mechanically locked. Please solve it. 
  If the  output is  unbalanced or  lost, the  inverter drive board  or  the output module 
may be damaged, ask for support. 
The inverter displays normally when power on, but switch at the input side trips 
when running: 
  Inspect whether the output side of inverter is short circuit. If yes, ask for support. 
  Inspect whether ground fault exists. If yes, solve it. 
  If trip happens occasionally and the distance between motor and inverter is too far, 
it is recommended to install output AC reactor.