CHV180 series frequency inverter special for elevator                                                  Wiring 
.18. 
SR T
Grid
 
Figure 4.9      Wiring of regenerative unit. 
4.4.5 Ground wiring (PE) 
Ground the PE terminal of the inverter with grounding resistors (less than 10
) for the 
insurance  of safety  and  avoidance  of  electrical shock  and  fire. It  is  apporiate to  use 
thick and short multiple copper core wires whose sectional area is larger than 3.5m ㎡. 
It is not recommended to use the public earth wire; otherwise, the grounding wires may 
complete the circuit. 
4.5 Wiring control circuit terminals 
4.5.1 Precautions 
  Use shielded or twisted-pair cables to connect control terminals.   
  Connect the ground terminal (PE) with shield wire.   
  The cable  connected to  the  control  terminal should  leave  away from the  main 
circuit  and  heavy  current  circuits  (including  power  supply  cable,  motor  cable, 
relay and contactor connecting cable) at least 20cm and parallel wiring should be 
avoided.  It  is  suggested  to  apply  perpendicular  wiring  to  prevent  inverter 
malfunction caused by external interference. 
4.5.2 Control circuit terminals 
Terminal  Description 
S1~S6 
ON-OFF  signal  input,  optical  coupling  isolation  input  terminal 
with PW and COM. 
Input voltage range: 9~30V 
Input impedance: 3.3kΩ 
PW  External  power  supply.  +24V  terminal  is  connected  to  PW