User manual of EC160 elevator intelligent integrated machine Function parameters
109
set to be 0 and the NC to be 1. Write the convertering decimal result to logic 2.
Above switches 9 and 10 are NC, and others are NO, which can be shown in binary 00000011,
converted into decimal (1+2)=003.
Logic setting 3 is the logic setting of the following signals:
Terminal P24 P23 P22 P21 P20 P19 P18 P17
Definition
Safety
high
voltage
detection
UPS
input
signal
Fire
action
signal
Motor
thermal
protection
Brake
travel
switch
detection
Brake
contactor
detection
Output
contactor
detection
Door lock
contactor
detection
NO/NC ○ ○ ○ ○ ● ● ● ○
Binary 0 0 0 0 1 1 1 0
Decimal 0×128 0×64 0×32 0×16 1×8 1×4 1×2 0×1
H0_02
Logic
setting 3
8+4+2=14
17 to 24 (from low bit to high bit) are shown in binary numbers. The corresponding bit of NO points
set to be 0 and the NC to be 1. Write the convertering decimal result to logic 3.
Above switches 18-20 are NC, and others are NO, which can be shown in binary 00001110,
converted into decimal (2+4+8)=014.
Logic setting 4 is the logic setting of the following signals:
Terminal P32 P31 P30 P29 P28 P27 P26 P25
Definition
Self-
definition
input 3
Self-
definition
input 2
Self-
definition
input 1
Pre-
opening
adhesion
Pre-
opening
feedback
Hardware
enabling
Hall door
lock high
voltage
detection
Car door
lock high
voltage
detection
NO/NC ○ ○ ○ ○ ○ ○ ○ ○
Binary 0 0 0 0 0 0 0 0
Decimal 0×128 0×64 0×32 0×16 0×8 0×4 0×2 0×1
H0_03
Logic
setting 4
0
25 to 32 (from low bit to high bit) are shown in binary numbers. The corresponding bit of NO points
set to be 0 and the NC to be 1. Write the convertering decimal result to logic 1.
Above input are NO, which can be shown in binary 00000000, converted into decimal 000.