User manual of EC160 elevator intelligent integrated machine Function parameters
131
board after adjustment. The MF output in the car and car weighing
compensation are cancelled.
The parameter will not involve in default value reset.
Function
code
Instruction Setting range【default value】 Remarks
F0_18
Relative selection of elevator
running
0~65535【0】
Not modify
in running
0: no operation
1: calling below 32 floor connected to inside line
2: parallel calling scan in cycle
4: speed involved in parallel control calculation
8: communication IC card enabling
16: no number clearance of internal calling remote reverse enabling
32: home floor opening standby enabling
64: during home floor opening standby, energy saving enabling (door beam will automatically
cancel energy saving in the state.)
The parameter is multi-function selective. Several functions can be effective simultaneously by
adding corresponding values. For example, when enabling communication IC card, keeping
home floor opening and energy saving are necessary, set 8+32+64=104.
Function
code
Instruction Setting range【default value】 Remarks
F0_19 1387 encoder C/D sampling 0~65535【0】
Not modify
in running
When the synchronous master lacks comfortablity or the running current is high, and autotuning
angle is unstable, redo autotuning after modifying P3.06~P3.08 as follows: to guarantee validity
of sampling values, the motor runs at slow speed and rotates one cycle.
0: current sampling value
1: The Max. value in the latest running
2: The Min. value in the latest running
4: The average value in the latest running