Function
code
Name Detailed instruction of parameters
Default
value
F0.05
Floor opening mode of
parallel outside calling
0: Main elevator and sub-elevator opening at
the same time
1: Main elevator opening
2: Sub-elevator opening
0
F0.06
Reset mode of running
fault overtime
0: Manual reset
1: Return to leveling automatically
0
F0.07 MF definition of IND
0: Original definition
1: Keep opening delay
2: Select front/rear door
3: Fire fighter input
1
F0.08
Internal command limit
times
0: Invalid
1-5: Record signal times limit when LL
0
F0.09 Dual door control mode
0: Dual control box mode (need rear door logic
setting)
1: Single control box mode
1
F0.10 Fire output
0: Output after forced landing
1: Output only in the home floor after forced
landing
F0.11
Floor internal command
opening enabling
0: Disabled
1: Enabled
0
F0.12
LIN1 multi-function
definition
0~40
0~2: Reserved
3: Medium speed down forced
speed-changing switch
4: Medium speed up forced speed-changing
switch
5: High speed down forced speed-changing
switch
6: High speed up forced speed-changing
switch
7: Down limit
8: Up limit
24