Goodrive100-PV series solar pumping inverters Function parameters
-46-
Function
code
Name
Detailed illustration of parameters
Default
Modify
cannot exceed the upper limit.
P15.05
Lower frequency
of PI output
0.0%~P15.04 (100.0% corresponds to
P00.03)
P15.05 is used to limit the Min. value of
target frequency, and 100.0%
corresponds to P00.03.
After PI adjustment, the target frequency
cannot be less than the lower limit.
20.0%
P15.06
KP1
0.00~100.00
Proportion coefficient 1 of the target
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
5.00
P15.07
KI1
0.00~100.00
Integral coefficient 1 of the target
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
5.00
P15.08
KP2
0.00~100.00
Proportion coefficient 2 of the target
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
35.00
P15.09
KI2
0.00~100.00
Integral coefficient 2 of the target
frequency
The bigger the value is, the stronger the
effect and faster the adjustment is.
35.00