Goodrive200A inverters Function parameters
60
Function
code
Name Detailed instruction of parameters
Default
value
Modify
P06.20
The
correspondin
g AO1
output
to the upper
limit
output of 100% of the output value is different.
Please refer to each application for detailed
information.
10V (20 m A )
0.0% 100 .0 %
A
O
Setting range of P06.18 0.00V~10.00V
Setting range of P06.19 P06.17~100.0%
Setting range of P06.20 0.00V~10.00V
Setting range of P06.21 0.000s~10.000s
Setting range of P06.22 0.0%~P06.24
Setting range of P06.23 0.00V~10.00V
Setting range of P06.24 P06.22~100.0%
Setting range of P06.25 0.00V~10.00V
Setting range of P06.26 0.000s~10.000s
Setting range of P06.27 0.000s~10.000s
Setting range of P06.28 0.00~50.00kHz
Setting range of P06.29 P06.27~100.0%
Setting range of P06.30 0.00~50.00kHz
Setting range of P06.31 0.000s~10.000s
10.00V
P06.21
AO1 output
filter time
0.000s
P06.22
L
ower limit of
AO2 output
0.0%
P06.23
Correspondin
g AO
2 output
to the lower
limit
0.00V
P06.24
Upper limit of
AO2 output
100.0%
P06.25
Correspondin
g AO
2 output
to the upper
limit
10.00V
P06.26
AO2 output
filter time
0.000s
P06.27
L
ower limit of
HDO output
0.00%
P06.28
Correspondin
g HDO
output to the
lower limit
0.00kHz
P06.29
Upper limit of
HDO output
100.0%
P06.30
Correspondin
g HDO
output to the
upper limit
50.00
kHz
P06.31
HDO output
filter time
0.000s