Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-72-
Analog
calibration
function
selection
DEC time of
emergency stop
0.0–6553.5s
0.0 indicates coast to stop.
The counter works by the input pulse signals of
the HDI terminals.
When the counter achieves a fixed number, the
multifunction output terminals will output the
signal of "Designated counting number arrival"
and the counter go on working; when the counter
achieves a set number, the multifunction output
terminals will output the signal of "Set counting
number arrival", the counter will clear all
numbers and stop to recount before the next
pulse.
The designated counting value P08.26 should be
no more than the set counting value P08.25.
Y1
RO1, RO2
S terminal
Reach the set
counting value
Reach the designated
counting value
P08.25 setting range: P08.26–65535
P08.26 setting range: 0–P08.25
Designated
counting value
This function code indicates the preset running
time of the VFD. When the accumulative running
time achieves the set time, the multifunction
digital output terminals will output the signal of
"running time arrival".
Setting range: 0–65535min
Automatic fault
reset times
Automatic fault reset times: When the VFD
selects automatic fault reset, it is used to set the
times of automatic reset. If the number of
continuous reset times exceeds the value, the
VFD will report a fault and stop.
Automatic fault reset interval: Time from when a
Automatic fault
reset interval