Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-74-
Y,
RO1, RO2
Output
frequency
Set
frequency
Detection
range
Time t
Time t
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
Running mode
of cooling fan
0: Common running mode
1: The fan keeps running after power on
0x000–0x0021
Ones: PWM mode
0: 3PH modulation and 2PH modulation
1: 3PH modulation
Tens: PWM low-speed carrier frequency limit
0: Limit low-speed carrier frequency to 1K or 2K
1: Limit low-speed carrier frequency to 4K
2: No limit on low-speed carrier frequency
Ones:
0: Overmodulation is invalid
1: Overmodulation is valid
Tens
0: Mild overmodulation
1: Deepened overmodulation
Keypad digit
control setting
0x0000–0x1223
LED ones: frequency enabling selection
0: Both ∧/∨ key adjustment and analog
potentiometer adjustment are valid
1: Only ∧/∨ key adjustment is valid
2: Only analog potentiometer adjustment is valid
3: Neither ∧/∨ key adjustment nor digital
potentiometer adjustment is valid