Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-84-
selection for
steps 0–7 in
simple PLC
running
After you select the corresponding
acceleration/deceleration time, convert the
combined 16-bit binary to a decimal, and then
set the corresponding function codes.
Setting range: -0x0000–0xFFFF
ACC/DEC time
selection for
steps 8–15 in
simple PLC
running
0: Restart from the first step; stop during running
(caused by the stop command, fault or power
loss), run from the first step after restart.
1: Continue to run from the stop frequency; stop
during running (cause by stop command and
fault), the VFD will record the running time
automatically, enter the step after restart and
keep the remaining running at the set frequency.
Multi-step time
unit selection
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is
counted by minute
P11 Protective parameters
0x000–0x111
LED ones: Phase loss software protection on the