Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-85-
Function
code
Name
Description
Default
value
Modify
input side
0: Disable
1: Enable
LED tens: Phase loss software protection on the
output side
0: Disable
1: Enable
LED hundreds: Phase loss hardware protection
on the input side
0: Disable
1: Enable
lower)
110
(4kW
and
higher)
P11.01
Frequency
decreasing at
sudden power
loss
0: Disable
1: Enable
0
P11.02
Frequency
decreasing rate
at sudden power
loss
Setting range: 0.00Hz/sP00.03 (Max. output
frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency decreasing point,
the VFD begins to decrease the running
frequency according to P11.02, to make the VFD
generate power again. The returned power can
maintain the bus voltage to ensure normal
running of the VFD until the recovery of power.
Voltage class
Frequency
decreasing
point at
sudden power
loss
380V
460V
Note:
Adjust the parameter properly to prevent the
stop caused by VFD protection during the
switching of the grid.
Prohibit input phase loss protection to enable
this function.
10.00
Hz/s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive18 Series and is the answer not in the manual?

INVT Goodrive18 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive18 Series
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals