Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-93-
Relay output
interaction
control
0: Invalid
1: Valid
When it is invalid, #1 inverter unit cannot control
output of RO2, and #2 inverter unit cannot
control output of RO1.
When it is valid, if F06.04 is invalid (#2 inverter
unit does not control output of RO2), #1 inverter
unit can control output of RO2; similarly, if
F06.03 is invalid (#1 inverter unit does not
control output of RO1), #2 inverter unit can
control output of RO1.
AI data
interaction
control
0: Invalid
1: Valid
When it is invalid, #1 inverter unit cannot read
AI3 of #2 inverter unit, and #2 inverter unit
cannot read AI2 of #1 inverter unit.
When it is valid, #1 inverter unit can read AI3 of
#2 inverter unit, and #2 inverter unit can read AI2
of #1 inverter unit.
AO data
interaction
control
0: Invalid
1: Valid
When it is invalid, #1 inverter unit cannot control
output of AO2, and #2 inverter unit cannot
control output of AO1.
When it is valid, if F06.15 is invalid (#2 inverter
unit does not control output of AO2), #1 inverter
unit can control output of AO2; similarly, if
F06.14 is invalid (#1 inverter unit does not
control output of AO1), #2 inverter unit can
control output of AO1.
Communication
interaction
action selection
at fault
0: The local device keeps running when another
device encounters a fault.
1: The local device coasts to stop and displays
the fault code when another device encounters a
fault.
When it is 0, if the dual system is running
properly, but #2 inverter unit (or #1 inverter unit)
encounters a fault, #1 inverter unit (or #2 inverter
unit) keeps running.