14. Verify or enter Flow rates (Air Rate): Open, Check, Other settings. Itron recommended typ-
ical settings are listed. For metric flow rates: choose from the flow rate dropdown list options.
These convert the Imperial (CFH) flow rates to Metric (CMH). The Other flow rate is not
required if the Test Revs: Index-Other is set to 0.
Open: 250
Check: 50
Other: 125
11 December 2019 TDC-1782-005 50
Intelis Gas Meter Installation Guide 5 Proving