EasyManua.ls Logo

ITT Hydrovar - Page 41

ITT Hydrovar
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
Programming
22
22 SELECT DEVICE
Select device
* 1 *
Possible settings: 1-8
Check the current status, the motor hours and the most recent failures of any given drive. The drive selec-
tion is determined by the current selected mode [105]. Select desired unit by pressing or .
CASCADE SERIAL/SYNCHRON:
The selection specifies the address of the HYDROVAR units
E.g. Device 1 -> Master Inverter with pre-selected address 1
Device 2 -> Basic Inverter with pre-selected address 2
Device 3 -> Basic Inverter with pre-selected address 3
To set the address on a Basic Inverter, see chapter addressing.
To set the address on a Master Inverter, see parameter [106] or submenu [1200] RS485-Interface.
Mode CASCADE RELAY:
Device Enabled By
1 Master Inverter
2 fixed speed pump Relay 1 X10: 1
3 fixed speed pump Relay 2 X10: 2
4 fixed speed pump Relay 3 X10: 3
5 fixed speed pump Relay 4 X10: 4
6 fixed speed pump Relay 5 X10: 5
7 not used
8 not used
23
23 STATUS DEVICE
Status of the selected device
Stopped
Possible messages: Running, Stopped, Disabled, OFF, Preparing (Mode Casc. Serial/Synchr)
relay on, relay off (Mode: Cascade Relay)
Solorun, Faulted (all Modes)
Shows the status of the device
Mode CASCADE RELAY:
relay_on -> Relay contact is closed -> xed-speed-pump is running
relay_off -> Relay contact is opened -> xed-speed-pump is stopped
S
G
S

Other manuals for ITT Hydrovar

Related product manuals