SPECIFICATIONS
ELECTRICAL REQUIREMENTS
i
Local codes may require more stringent protection than what is displayed here and on the data plate. Always verify with your electrical
service contractor that your circuit protection is adequate and meets all applicable national and local codes. Numbers in this manual are
for reference and may change without notice.
On three-phase machines, imbalanced wild leg goes to L3. Also see the Motor Rotation section.
Information below is for machine components only. If using a third-party external booster, consult booster manufacturer for booster
information. For steam booster information, see Steam Line Connections section.
AJX-80/90CE
Volts Phase Freq
Pre-wash
Motor
Wash
Motor
Drive
Motor
Wash
Heater
Total Load MCA MOP
208 1 60 Hz 8.7 A 8.7 A 1.8 A 86.5 A 105.7 A 107.9 A 115 A
208 3 60 Hz 5.8 A 5.8 A 1.2 A 50.0 A 62.8 A 64.2 A 70 A
230 3 60 Hz 5.7 A 5.7 A 1.1 A 41.5 A 54.0 A 55.4 A 60 A
460 3 60 Hz 2.9 A 2.9 A 0.6 A 20.7 A 27.0 A 27.7 A 30 A
AJX-80/90CS
Volts Phase Freq
Pre-wash
Motor
Wash
Motor
Drive
Motor
Wash
Heater
Total Load MCA MOP
208 3 60 Hz 3.3 A 5.8 A 1.2 A N/A 10.3 A 11.8 A 15 A
460 3 60 Hz 2.9 A 2.9 A 0.6 A N/A 6.3 A 7.0 A 15 A